| Item | Specification |
| Product Model | Example: S22-M-100/10 (S=Three-Phase; 22=Top Efficiency Class; 100=kVA; 10=HV kV) |
| Rated Capacity | 30kVA~2500kVA |
| Phase/Frequency | Three-Phase; 50Hz/60Hz (±1% tolerance) |
| Connection Group | Dyn11 (standard) |
| Core Structure | Three-phase three-limb wound core (inner-outer frame winding) |
| Parameter | Detail |
| Ambient Temperature | -25℃~40℃ (optional -40℃ with anti-freeze) |
| Altitude | ≤1000m (5% derating at 1500m) |
| Humidity | ≤90% @25℃ (no condensation) |
| Protection Class | IP23 (outdoor) / IP20 (indoor) |
| Service Life | 20 years (normal maintenance) |
| Parameter | Value | Test Condition |
| No-Load Loss (Po) | ≤120W (S22 class) | Rated voltage/frequency |
| Load Loss (Pk) | ≤1140W | Rated current, 75℃ |
| Impedance (Uk%) | 4%~5% | 75℃, ±10% tolerance |
| No-Load Current (Io%) | ≤0.8% | Rated voltage |
Adopting advanced winding technology, it achieves an energy efficiency of up to 98%, significantly reducing energy loss. This cuts users' operational costs substantially in long-term use and meets energy-saving and consumption-reduction requirements.
With an exquisite structural design, it has a smaller volume, which can flexibly fit into various installation scenarios such as industrial workshops and power distribution rooms. It saves limited site space and simplifies layout planning.
It features excellent electrical stability and is paired with high-insulation-strength materials, effectively resisting interference like voltage fluctuations. Moreover, it has a long service life, reducing the frequency of maintenance and replacement and ensuring continuous equipment operation.
It supports customized specifications based on customers' personalized needs such as power, voltage, and installation method. It can accurately match different application scenarios including power distribution, industrial equipment, and new energy systems, meeting diverse usage requirements.
Leverages advanced winding craftsmanship to reach 98% efficiency, aligning with global emission standards.
Streamlined structural design enables flexible installation in workshops and power distribution rooms.
Withstands voltage fluctuations with high-insulation materials, ensuring uninterrupted operation.
Tailored specifications perfectly adapt to solar, wind power, and other diverse industrial machinery setups.